⚡ Cable Length & Voltage Drop

Calculate voltage drop and select proper cable size for your electrical projects. ⚠️ Always verify with local electrical codes and professionals.
🔌 Electrical Parameters:
Amps
Volts
%
Common Scenarios:
⚠️ Electrical Safety & Best Practices
Formula: Vdrop = 2 × L × I × R / 1000
Voltage drop = 2 × Length(ft) × Current(A) × Resistance(Ω/kft)
⚠️ Critical Safety
• Always hire licensed electricians
• Follow NEC/ local codes
• Use proper circuit protection
AWG vs mm²
• 14 AWG = 2.08 mm² (15A max)
• 12 AWG = 3.31 mm² (20A max)
• 10 AWG = 5.26 mm² (30A max)
Pro Tips
• Calculate round-trip distance
• Factor in temperature rating
• Consider future expansion
• Use voltage drop tables
📋 Copper Wire Resistance (Ω per 1000 ft):
AWG mm² Resistance (Ω/kft) Max Current*
180.826.38510A
161.314.01613A
142.082.52515A
123.311.58820A
105.260.998930A
88.370.628240A
* For chassis wiring, not building wiring
Disclaimer:
This tool provides educational estimates only. Actual cable sizing requires compliance with local electrical codes (NEC, IEC, etc.) and professional engineering review.